ENGINEERING DATA
Overall size of ceiling module with built in recirculating fan
3800x3800 2780x2780 60mm min
Size of clean zone
Depth of unit below ceiling (variable) Supply air volume (normal airflow)
2.9401m3/sec Average downflow velocity at lower canopy edge 0.38m3/sec Approx. room air change if air supplied into UCV 100x per hr Filtration standard
Final filters: 99.999% on HOT Dop to AS4260 Prefilters: 85% to AS1324 (No.4 Dust) Single phase, nom 3.9kW
Electrical rating (high speed, including fluorescent lights)
ON-SITE TESTING
UCV Systems and filters are factory tested and certified by a NATA-Accredited laboratory. Additional testing and certification is recommended as follows:
• On site prior to use • After maintenance • After filter replacement
• After re-location • At least annually • In special circumstances, e.g. if faulty operation is suspected.
THE COMPANY AES Environmental is an Australian owned manufacturing business producing products under Clyde-Apac, Email Air Handling and Vokes brand names for industries that are as varied as industrial plants, commercial buildings, power stations, food processing, healthcare, science and electronics. AES Environmental considers the Australian Standards as a core component of its product mix and has developed an export market in 25 countries, promoting Australian Standards, engineering and manufacturing solutions. AES Environmental, a trusted manufacturer capable of delivering reliable product solutions to highly-critical applications, where the control of hazardous airborne contamination is often critical to process and personnel.
© 2017 AES Environmental | Bulletin No. 1Ϯ:.01.17 AES107 REV1 In keep ing with our policy of continuing product improvement, we reserve the right to alter specifications without notice.
Powered by FlippingBook